KME can give you complete technical support for the correct cable selection.
The MICO® catalogue contains complete dimensional and electric characteristics for high temperature and critical applications.
Contact us for all your requirements!

Additionally you will receive information concerning the following:

  • insulation dielectric strength
  • current ratings
  • volt drop

 

Light duty multi-cables (500 V): resistance, reactance and impendance

Cable Type

Resistance R (Ω/km)

Reactance X (Ω/km)

Impedance Z (Ω/km)

30 °C

70 °C

105 °C

 

30 °C

70 °C

105 °C

2 L 1

18.811

21.656

24.145

0.088

18.811

21.656

24.145

2 L 1,5

12.575

14.477

16.141

0.083

12.576

14.477

16.141

2 L 2,5

7.701

8.866

9.885

0.079

7.702

8.866

9.885

2 L 4

4.479

5.157

5.749

0.075

4.480

5.157

5.749

3 L 1

18.811

21.656

24.145

0.091

18.811

21.656

24.145

3 L 1,5

12.575

14.477

16.141

0.086

12.576

14.477

16.141

3 L 2,5

7.701

8.866

9.885

0.079

7.702

8.866

9.885

These values are valid also for multi-core cables with 4 & 7 conductors

 

Single-core triplet cables: resistance, reactance & impendance

Cable Type

Resistance R (Ω/km)

Reactance X (Ω/km)

Impedance Z (Ω/km)

30 °C

70 °C

105 °C

 

30 °C

70 °C

105 °C

 1 H 1,5

12.576

14.478

16.142

0.139

 12.577

14.478

16.142

 1 H 2,5

7.702

8.866

9.885

0.128

7.703

8.867

9.886

 1 H 4

4.792

5.516

6.15

0.120

4.793

5.518

8.650

 1 H 6

3.202

3.686

4.109

0.112

3.204

3.687

4.111

 1 H 10

1.903

2.190

2.442

0.104

1.906

2.193

2.444

 1 H 16

1.196

1.377

1.535

0.098

1.200

1.380

1.538

 1 H 25

0.757

0.871

0.971

0.093

0.763

0.876

0.975

1 H 35

0.546

0.628

0.700

0.089

0.554

0.635

0.706

1 H 50

0.404

0.465

0.518

0.085

0.413

0.473

0.525

1 H 70

0.281

0.323

0.360

0.083

0.293

0.333

0.369

1 H 95

0.204

0.234

0.260

0.080

0.219

0.247

0.272

1 H 120

0.163

0.186

0.207

0.078

0.180

0.202

0.221

1 H 150

0.133

0.152

0.169

0.077

0.154

0.170

0.185

1 H 185

0.109

0.123

0.137

0.076

0.133

0.145

0.157

1 H 240

0.086

0.096

0.106

0.076

0.115

0.123

0.131

1 H 300

0.076

0.084

0.092

0.075

0.107

0.113

0.119

1 H 400

0.075

0.063

0.069

0.075

0.095

0.099

0.103

 

Heavy duty two-core cables (750 V): resistance, reactance & impendance

Cable Type

Resistance R (Ω/km)

Reactance X (Ω/km)

Impedance Z (Ω/km)

30 °C

70 °C

105 °C

 

30 °C

70 °C

105 °C

2 H 1,5

12.575

14.477

16.141

0.101

12.576

14.478

16.142

2 H 2,5

7.701

8.886

9.885

0.094

7.702

8.866

9.885

2 H 4

4.791

5.516

6.150

0.088

4.792

5.516

6.150

2 H 6

3.200

3.685

4.109

0.083

3.201

3.686

4.110

2 H 10

1.902

2.190

2.441

0.079

1.904

2.191

2.442

2 H 16

1.195

1.376

1.534

0.075

1.198

1.378

1.536

2 H 25

0.756

0.870

0.970

0.073

0.759

0.873

0.973

These values are applicable also for all the other types of multi-core cables (3,4,7,12 & 19 conductors)