KME can give you complete technical support for the correct cable selection.
The MICO catalogue contains complete dimensional and electric characteristics for high temperature and critical applications.
Contact us for all your requirements!

Additionally you will receive information concerning the following:

  • insulation dielectric strength
  • current ratings
  • volt drop

 

Light duty multi-cables (500 V): resistance, reactance and impendance

Cable Type

Resistance R (Ω/km)

Reactance X (Ω/km)

Impedance Z (Ω/km)

30 °C

70 °C

105 °C

 

30 °C

70 °C

105 °C

2 L 1

18.811

21.656

24.145

0.088

18.811

21.656

24.145

2 L 1,5

12.575

14.477

16.141

0.083

12.576

14.477

16.141

2 L 2,5

7.701

8.866

9.885

0.079

7.702

8.866

9.885

2 L 4

4.479

5.157

5.749

0.075

4.480

5.157

5.749

3 L 1

18.811

21.656

24.145

0.091

18.811

21.656

24.145

3 L 1,5

12.575

14.477

16.141

0.086

12.576

14.477

16.141

3 L 2,5

7.701

8.866

9.885

0.079

7.702

8.866

9.885

These values are valid also for multi-core cables with 4 & 7 conductors

 

Single-core triplet cables: resistance, reactance & impendance

Cable Type

Resistance R (Ω/km)

Reactance X (Ω/km)

Impedance Z (Ω/km)

30 °C

70 °C

105 °C

 

30 °C

70 °C

105 °C

 1 H 1,5

12.576

14.478

16.142

0.139

 12.577

14.478

16.142

 1 H 2,5

7.702

8.866

9.885

0.128

7.703

8.867

9.886

 1 H 4

4.792

5.516

6.15

0.120

4.793

5.518

8.650

 1 H 6

3.202

3.686

4.109

0.112

3.204

3.687

4.111

 1 H 10

1.903

2.190

2.442

0.104

1.906

2.193

2.444

 1 H 16

1.196

1.377

1.535

0.098

1.200

1.380

1.538

 1 H 25

0.757

0.871

0.971

0.093

0.763

0.876

0.975

1 H 35

0.546

0.628

0.700

0.089

0.554

0.635

0.706

1 H 50

0.404

0.465

0.518

0.085

0.413

0.473

0.525

1 H 70

0.281

0.323

0.360

0.083

0.293

0.333

0.369

1 H 95

0.204

0.234

0.260

0.080

0.219

0.247

0.272

1 H 120

0.163

0.186

0.207

0.078

0.180

0.202

0.221

1 H 150

0.133

0.152

0.169

0.077

0.154

0.170

0.185

1 H 185

0.109

0.123

0.137

0.076

0.133

0.145

0.157

1 H 240

0.086

0.096

0.106

0.076

0.115

0.123

0.131

1 H 300

0.076

0.084

0.092

0.075

0.107

0.113

0.119

1 H 400

0.075

0.063

0.069

0.075

0.095

0.099

0.103

 

Heavy duty two-core cables (750 V): resistance, reactance & impendance

Cable Type

Resistance R (Ω/km)

Reactance X (Ω/km)

Impedance Z (Ω/km)

30 °C

70 °C

105 °C

 

30 °C

70 °C

105 °C

2 H 1,5

12.575

14.477

16.141

0.101

12.576

14.478

16.142

2 H 2,5

7.701

8.886

9.885

0.094

7.702

8.866

9.885

2 H 4

4.791

5.516

6.150

0.088

4.792

5.516

6.150

2 H 6

3.200

3.685

4.109

0.083

3.201

3.686

4.110

2 H 10

1.902

2.190

2.441

0.079

1.904

2.191

2.442

2 H 16

1.195

1.376

1.534

0.075

1.198

1.378

1.536

2 H 25

0.756

0.870

0.970

0.073

0.759

0.873

0.973

These values are applicable also for all the other types of multi-core cables (3,4,7,12 & 19 conductors)


CONTACT